Products and Services
|
Model
|
SDKW1L-100
|
SDKW1L-225
|
SDKW1L-400
|
SDKW1L-630, 800
|
|||||||||||
|
Frame Size Rated Current (Inm)(A)
|
100
|
225
|
400
|
630, 800
|
|||||||||||
|
Rated Current (In)(A)
|
10, 16, 20, 25, 32
|
100, 125, 140, 160
|
225, 315
|
400, 500, 630
|
|||||||||||
|
40, 50, 63, 80, 100
|
180, 200, 225
|
350, 400
|
700, 800
|
||||||||||||
|
Number of Poles
|
2
|
3
|
4
|
2
|
3
|
4
|
3
|
4
|
3
|
4
|
|||||
|
Rated Insulation Voltage (Ui)(V)
|
AC800
|
||||||||||||||
|
Rated Working Voltage (Ue)(V)
|
AC400
|
||||||||||||||
|
Rated Impulse Withstand Voltage (Uimp)(V)
|
8000
|
||||||||||||||
|
Flashover Distance
|
50
|
100
|
|||||||||||||
|
Breaking Capacity Level
|
L
|
M
|
H
|
L
|
M
|
H
|
L
|
M
|
H
|
L
|
M
|
H
|
|||
|
Ultimate Short Circuit Breaking Capacity
(Icu)(kA) |
30
|
50
|
85
|
30
|
50
|
85
|
50
|
65
|
100
|
50
|
65
|
100
|
|||
|
Service Short Circuit Breaking Capacity
(Ics)(kA) |
15
|
35
|
50
|
15
|
35
|
50
|
35
|
42
|
65
|
35
|
42
|
65
|
|||
|
Rated Residual Short Circuit Making (Breaking) Capacity
|
8.75
|
12.5
|
21
|
8.75
|
12.5
|
21
|
12.5
|
13.5
|
25
|
12.5
|
13.5
|
25
|
|||
|
Rated Residual Operating Current (I△n)(mA)
|
No delay
|
30/100/500, 100/300/500
|
30/100/500, 100/300/500
|
100/300/500
|
300/500/1000
|
||||||||||
|
Delay
|
100/300/500
|
100/300/500
|
100/300/500
|
300/500/1000
|
|||||||||||
|
Rated Residual Non-operating Current
(I△n)(mA) |
1/21△n
|
1/21△n
|
1/21△n
|
1/21△n
|
|||||||||||
|
Operating Performance (Number of Times)
|
Switch on
|
1500
|
1000
|
1000
|
1000
|
||||||||||
|
Switch off
|
8500
|
7000
|
4000
|
4000
|
|||||||||||
|
Total
|
10000
|
80000
|
5000
|
5000
|
|||||||||||
|
Residual Current Operating Time of Protection
|
I△n
|
2I△n
|
5I△n
|
10I△n
|
|||||||||||
|
Maximum Breaking Time (S)
|
No delay
|
0.2
|
0.1
|
0.04
|
0.04
|
||||||||||
|
Delay
|
0.5/1.15/2.15
|
0.35/1/2
|
0.25/0.9/1.9
|
0.25/0.9/1.9
|
|||||||||||